23 74 13
Packaged Rooftop Units: submittal requirements
HVAC packages are equipment-heavy, and every unit gets checked against the schedule: capacity, electrical, dimensions, and sound. Ductwork, insulation, and air distribution ride along with their own data.
What reviewers expect in a packaged rooftop units package
- Equipment data keyed to schedule tags with capacities at the scheduled conditions
- Electrical characteristics (MCA, MOCP, voltage) matching the electrical drawings
- Fan curves with the operating point plotted
- Diffuser/register/grille schedule with sizes, throws, and NC ratings
- Duct construction standards and insulation data (R-value, jacket, thickness)
- Vibration isolation and seismic restraint details where specified
- Controls sequence compatibility — points list matching the BAS spec
Field tip
Highlight the scheduled operating point on every fan curve and capacity table. Reviewers reject packages where they have to find it themselves — marked curves get approved.
Manufacturers we see in 23 74 13 packages
From our catalog of 335,000+ products with data sheets: 601 packaged rooftop units products across 43manufacturers. The spec's approved list always governs.
- Lutec Virtuo — Lutec
- Artuce Perche — Artuce
- Pallucco Fortuny — Pallucco
- Artuce Tools_2013 — Artuce
Build this package in minutes
Tell the builder what your packaged rooftop units scope needs — or upload the 23 74 13 spec — and it finds the cut sheets, assembles the package with a cover and transmittal, and lets you refine it in chat. First packages are free.
Build a 23 74 13 submittal freeCommon questions
What goes in a 23 74 13 packaged rooftop units submittal?
Product data sheets for every item in the section, keyed to the drawings or schedules, plus whatever the spec's Part 1 lists — commonly shop drawings, samples, certifications, and warranty terms. The checklist above covers what reviewers look for first.
Which manufacturers are common in 23 74 13 packages?
Across our catalog we hold 601 packaged rooftop units products from 43 manufacturers, led by Carrier, nVent HOFFMAN, Trane. The spec's approved-manufacturer list always governs — check Part 2 before you commit.
How do I build this package faster?
Describe the scope to the Submittal.app builder or upload the spec section — it finds the cut sheets, assembles the package with a cover and transmittal, and lets you refine everything in chat. First packages are free.